Products
Experience The Best World-Class Comprehensive Energy Service Provider
HXGN-12 SF6 Gas Fully Insulated Ring Main Unit and Outdoor Ring Main Box
Drawing on years of product design and manufacturing experience, we developed this SF6 gas-insulated ring main unit using computer simulation technology. The combination of common-chamber and unit-type configurations suits network nodes and customer terminals, while also meeting the need of various secondary substations for compact switchgear. The RMU gas tank is a completely sealed system: all live parts and switching functions are enclosed in a 304 stainless steel tank.
HXGN-12 SF6 Gas Fully Insulated Ring Main Unit and Outdoor Ring Main Box.pdf
Product Details
Drawing on years of product design and manufacturing experience, we developed this SF6 gas-insulated ring main unit using computer simulation technology. The combination of common-chamber and unit-type configurations suits network nodes and customer terminals, while also meeting the need of various secondary substations for compact switchgear. The RMU gas tank is a completely sealed system: all live parts and switching functions are enclosed in a 304 stainless steel tank. The entire switchgear is immune to external environmental conditions, ensuring operational reliability, personnel safety and maintenance-free operation. Fully insulated, shielded extension busbars enable various supply configurations. The RMU also supports factory-integrated automation solutions, realising the concept of smart switchgear and minimising on-site installation and commissioning work.
The outdoor ring main box is composed of SF6 gas-insulated ring main unit and outdoor box. The enclosure is generally made of powder-coated aluminium-zinc (Al-Zn) alloy-coated steel sheet or stainless steel sheet, with strong corrosion resistance. It can also be manufactured to materials specified by the user; patterns and decorative wood strips can be applied to the outer surface. The box parts are all sheet metal components, connected by riveting, bolting or welding. There are no fasteners on the box surface for disassembly, providing good anti-theft performance. The enclosure has a degree of protection of IP43 and good weatherproofing. The roof is a double-skin structure with an air gap and ventilation openings, creating natural air convection from bottom to top for good thermal insulation and ventilation. The roof has a drainage slope of at least 3 degrees. The enclosure is compact and space-saving, without obstructing the line of sight. The RMU can be installed and fully tested in the enclosure at the factory, eliminating the need for on-site construction of a distribution room and reducing investment costs for users.
Technical Specifications
|
Model |
HXGN-12 |
Rated Voltage |
12kV |
|
Rated Current |
630A |
Rated Frequency |
50Hz |
|
Rated Short-circuit Breaking Current |
20kA |
Rated Short-time Withstand Current/Duration |
20 kA / 4 s |
|
Rated Peak Withstand Current |
50kA |
Rated Lightning Impulse Withstand Voltage (Phase-to-phase and phase-to-earth) |
75kV |
|
Rated Lightning Impulse Withstand Voltage (across the isolating distance) |
85 kV |
Rated Short-time Power Frequency Withstand Voltage (Phase-to-phase and phase-to-earth) |
42kV |
|
Rated Short-time Power Frequency Withstand Voltage (Across open contacts) |
48kV |
Main Circuit Resistance (Single Phase) |
≤180μΩ (C unit), ≤580μΩ (F unit), ≤180μΩ (V unit), ≤150μΩ (Ring main box) |
|
Mechanical Life |
Circuit Breaker/Load Switch: 5000 times (C), 5000 times (F), 20000 times (V), 20000 times (Ring main box); Isolating/Earthing Switch: 5000 times |
Electrical Life |
Circuit Breaker/Load Switch: 200 times (C), 200 times (F), 30 times (V), 30 times (Ring main box); Earthing Switch Making: 5 times |
|
Auxiliary Circuit Control Voltage |
DC24/48/110, AC/DC220 |
Internal Arc Classification |
AFLR 20/1 (C), AFLR 20/1 (F), AFLR 20(25)/1 (V), AFLR 20(25)/1 + BFLR 20(25)/1 (Ring main box) |
|
Enclosure Protection Rating |
IP4X (C/V/F), IP43 (Ring main box) |
Gas Compartment Protection Rating |
IP67 |
|
SF6 Rated Filling Pressure (gauge, at 20 °C) |
0.13 MPa |
Annual Gas Leakage Rate |
≤0.01% |
Applications
Suitable for network nodes or user terminals, and meets the flexible use requirements of various secondary substations for compact switchgear. Widely used in industrial and civil ring network and terminal power supply. Especially suitable for small secondary distribution stations, switching stations, industrial and mining enterprises, airports, railways, commercial areas, high-rise buildings, highways, subways, tunnels and other fields.
Scope of Use and Precautions
Applicable range:
Normal environmental conditions:
The ring main unit operates under normal indoor conditions and within outdoor ring main boxes, complying with GB/T 3906 and GB/T 11022.
Maximum ambient air temperature: +60℃
Minimum ambient air temperature: -25/-40℃
Maximum daily temperature difference: 25 K
Altitude: ≤ 2,000 m
Solar radiation intensity: 0.1 W/cm²
Pollution level: IV
Ice coating thickness: 10mm
Wind speed/wind pressure: 34m/s / 700Pa
Daily average relative humidity: ≤95%; Monthly average relative humidity: ≤90%
Seismic resistance (horizontal acceleration): 2m/s²
Note 1: If the temperature falls below −25 °C or the altitude exceeds 2,000 m, please contact us so that the technical parameters can be adjusted during production.
Precautions:
Acceptance and installation precautions: After receiving the HXGN□-12 SF6 gas-insulated ring main unit, the user should carry out the following acceptance work:
Check whether the packaging is intact. If damaged, please note on the receipt.
Check the technical parameters on the nameplate and verify that the product certificate conforms to the ordering requirements.
All components should be intact, with no obvious discharge traces, and the connection contact surfaces should have no obvious overheating. Any unqualified components should be notified to the manufacturer for replacement.
Check the product accessories and factory documents against the packing list.
All parameters of this product have been adjusted and inspected before leaving the factory, and users do not need to adjust them. Before installation, check whether the operating mechanism is normal, and carry out handover tests as required. The external cable terminal of the incoming and outgoing bushings must be connected to the bushing with bolts (the cable terminal can be supplied with the cabinet); Cable terminations must be prepared securely and reliably by qualified personnel. The cabinet must be firmly installed on the foundation, fixed, and have a good grounding device. Incoming and outgoing cables are routed in or out through cable terminations. If overhead incoming and outgoing lines are required, they can be led to overhead lines through cables.
Typical Solution
Product Parameters
Product Basis Standards:
• GB/T 3906 3.6 kV–40.5 kV AC metal-enclosed switchgear and controlgear
• GB/T 11022 Common Specifications for High-voltage AC Switchgear and Controlgear Standards
• GB/T 1984 High-voltage AC Circuit Breakers
• GB/T 1985 High-voltage AC Disconnectors and Earthing Switches
• GB/T3804 3.6 kV–40.5 kV High-voltage AC Load Break Switches
• GB/T 16926 High-voltage AC switch-fuse combinations
• DL/T 402 Ordering Technical Conditions for High-voltage AC Circuit Breakers
• DL/T 593 Common Technical Requirements for High-voltage Switchgear and Controlgear Standards
• DL/T 404 3.6 kV–40.5 kV AC Metal-enclosed Switchgear and Controlgear
• Electrical interlocking and control circuit: On the basis of the manual mechanism, closing and tripping coils and auxiliary contacts can be added as required to meet electric operation and distribution automation functions.
• Sealed operating mechanism (suitable for humid areas): Our company independently developed a sealed operating mechanism suitable for humid areas on the basis of conventional mechanisms. The protection rating is IP65 and a type test report has been obtained, avoiding the impact of rust, corrosion and condensation on the service life of the operating mechanism.
• Voltage indication: the voltage indicator shows whether the unit is live, enables phase checking, and interlocks the earthing switch while the circuit is live.
• Cable accessories: The cable connection position of the ring main unit is equipped with standard C-type bushings. The cable is connected to the unit through European-standard separable connectors, and can meet the installation of double cables and surge arresters.
• Pressure gauge: each gas tank is fitted with a pressure gauge, optionally with output contacts, a gas refilling port and remote monitoring functions.
• Extension busbar: both unit-type coupling and common-chamber (block) extension use dedicated extension busbars — side or top extension. The busbar position and dimensions meet the requirements of the State Grid standardized design customization scheme.
• Secondary compartment: when the RMU is equipped for electric operation, protection devices, distribution automation equipment, opening/closing operation and indication and other secondary components can be installed separately in the secondary compartment.
• Intelligent digital functions: Through real-time status monitoring and diagnosis of temperature, insulating gas, mechanical characteristics, etc. of the ring main unit, it provides a quantified health index, predicts the likelihood of failure, prevents potential risks from developing into faults, and avoids unplanned outages.
• Temperature monitoring: Temperature monitoring is suitable for temperature monitoring at cable bushing connections. It uses self-powered technology to provide temperature-rise alarms, with judgments combined with environmental conditions.
• Insulating gas status monitoring: Insulating-gas status monitoring retains conventional operating habits and provides an intelligent pressure gauge with a mechanical pointer and digital real-time status output.
• Mechanical characteristics monitoring: Intelligent sensors are used to obtain state parameters of secondary components, and advanced mathematical models are used for real-time analysis and calculation to identify potential faults and monitor switch health status.
• Partial discharge detection device: High-frequency signal detection and analysis technology is used to perform distributed online detection on high-voltage switchgear, discover partial discharge signals in the ring main unit in real time, analyze the waveform characteristics of partial discharge pulses, automatically generate detection reports, and realize online insulation monitoring and diagnosis of the ring main unit.
• Intelligent distributed DTU: Our company independently developed and produced the distributed DTU KLD-9307, which can meet the needs of the State Grid, China Southern Power Grid and users for intelligent distributed distribution network automation. The implementation of this scheme mainly relies on the distributed DTU equipped in the ring main unit and the communication network, supports various distribution topology networks, effectively reduces system complexity and cost, and improves performance and reliability.
Certifications:
Product basis standards: GB/T 3906, GB/T 11022, GB/T 1984, GB/T 1985, GB/T3804, GB/T16926, DL/T 402, DL/T 593, DL/T 404, China Southern Power Grid Corporation Bidding Technical Specifications.
RELATED PRODUCTS
Find Solutions, Not Just Suppliers
If you are interested in any of our products or would like to make your customized order, please feel free to contact us. We are looking forward to establish successful business relations with you.
Discover More