KEXGN-40.5 Gas Insulated Metal-Enclosed Switchgear
KEXGN-40.5 gas insulated metal-enclosed switchgear (abbreviated as C-GIS) is our latest in-house development — a three-phase, 50 Hz indoor high-voltage distribution assembly with a rated voltage of 40.5 kV, which is used for receiving, controlling, distributing and protecting electrical energy in industrial and mining enterprises, power plants and substations.
KEXGN-40.5 Gas Insulated Metal-Enclosed Switchgear.pdf
Product Details
KEXGN-40.5 gas insulated metal-enclosed switchgear (abbreviated as C-GIS) is our latest in-house development — a three-phase, 50 Hz indoor high-voltage distribution assembly with a rated voltage of 40.5 kV, which is used for receiving, controlling, distributing and protecting electrical energy in industrial and mining enterprises, power plants and substations. This product offers high operational safety, immunity to climate, easy installation, minimal maintenance, a compact footprint, no exposed live parts, reliable long-term operation in harsh environments and flexible configuration via extension busbars. It is ideal for industrial and commercial areas with high load density, cable-fed networks or rural towns, compact substations, wind power and subway applications.
Technical Specifications
|
Model |
KEXGN-40.5 |
Rated Voltage |
40.5kV |
|
Rated Frequency |
50Hz |
Rated Current |
630, 1250, 2500, 3150A |
|
Power-frequency withstand voltage (1 min) |
95 kV phase-to-earth/phase-to-phase; 118 kV across the vacuum and isolating distance |
Lightning impulse withstand voltage |
185 kV phase-to-earth/phase-to-phase; 215 kV across the vacuum and isolating distance |
|
Rated short-time withstand current |
main circuit 25/31.5/40 kA; earthing switch 27.4/34.8 kA; earthing connection circuit 69.6/87 kA |
Rated peak withstand current |
main circuit 63/80/100 kA; earthing switch 69.6/87 kA; earthing connection circuit 69.6/87 kA |
|
Circuit Breaker Rated Short-circuit Breaking Current |
25, 31.5, 40kA |
Circuit Breaker Rated Short-circuit Making Current (Peak) |
63, 80, 100kA |
|
Circuit Breaker Rated Operating Sequence |
O–0.3 s–CO–180 s–CO |
Mechanical Life |
Circuit Breaker: 20000 times; Isolating Switch, Earthing Switch: 10000 times |
|
SF6 Gas Rated Pressure (gauge, at 20 °C) |
0.02 MPa |
SF6 Gas Minimum Working Pressure (20℃, gauge pressure) |
0MPa |
|
SF6 Gas Moisture Content |
≤ 150 µL/L |
SF6 Gas Leakage Rate |
≤0.01% per year |
|
Degree of Protection |
IP41 (enclosure), IP67 (gas compartment) |
Rated Supply Voltage for Closing/Opening Devices and Auxiliary Circuits |
DC 220 V / AC 220 V |
|
Internal Arc (AFLR) Fault Current |
25, 31.5, 40kA; Duration: 1s |
Safe and reliable. The gas tank features a single/double gas chamber design. Gas leakage in one gas chamber does not affect the insulation performance of the other chamber. The frame-type structure design greatly reduces the deformation of the gas tank. The tank is filled with SF6 gas at a relative pressure of 0.02 MPa. It can still maintain sufficient insulation strength at zero gauge pressure without affecting normal operation of equipment.
Strong environmental adaptability. All high-voltage components are sealed in stainless steel enclosures, and performance is not affected by external environmental factors. Especially suitable for harsh environments such as high altitude, severe cold, humidity, and pollution.
Low maintenance. High-voltage insulation is not affected by external environment and is not easy to age; vacuum switches are used to make and break short-circuit current, avoiding the shortcomings of earthing switches not being able to quickly make earthing current and requiring maintenance after making short-circuit; the gas tank adopts 3.0mm thick high-quality stainless steel plate, using robot welding; the most advanced helium mass-spectrometry leak detection method is used to detect gas leakage.
Applications
Can be used for receiving, controlling, distributing and protecting electrical energy in industrial and mining enterprises, power plants and substations. Very suitable for application in industrial and commercial areas with high load density, cable-fed networks or rural towns, box-type substations, wind power generation, subways and other fields.
Scope of Use and Precautions
Applicable range:
Normal use conditions:
Ambient temperature: Maximum temperature: +70℃; Minimum temperature: -40℃
Ambient humidity: Daily average relative humidity: ≤95%; Monthly average relative humidity: ≤90%
Altitude: Not exceeding 3000m
Seismic intensity: Not exceeding 8 degrees
Acceptance and installation precautions:
After receiving the KEXGN-40.5 gas insulated metal-enclosed switchgear, the user should carry out the following acceptance work:
Check whether the packaging is intact. If damaged, please note on the receipt.
Check the technical parameters on the nameplate and verify that the product certificate conforms to the ordering requirements.
All components should be intact, with no obvious discharge traces, and the connection contact surfaces should have no obvious overheating. Any unqualified components should be notified to the manufacturer for replacement.
Check the product accessories and factory documents for completeness against the packing list.
All parameters of this product have been adjusted and inspected before leaving the factory, and users do not need to adjust them. Before installation, check whether the operating mechanism is normal, and carry out handover tests as required. The external cable terminal of the incoming and outgoing bushings must be connected to the bushing with bolts (the cable terminal can be supplied with the cabinet); the cable head must be made firmly and reliably by professionals. The cabinet must be firmly installed on the foundation, fixed, and have a good grounding device. Incoming and outgoing cables are led in or out through cable terminals. If overhead incoming and outgoing lines are required, they can be led to overhead lines through cables.
Design Features
SolidWorks computer simulation solid modelling and virtual assembly;
ANSYS electromagnetic field finite element analysis and optimization design;
ADAMS 3D mechanism operation simulation, motion interference check;
Standardized cable entry/exit bushings and busbar connection bushings;
A comprehensive mechanical interlocking scheme (Five-prevention interlocks).
Typical Solution
Product Parameters
Product Basis Standards:
• GB/T 311.1 Insulation Coordination for High-voltage Transmission and Transformation Equipment
• GB/T 1985 AC High-voltage Disconnectors and Earthing Switches
• GB/T 1984 High-voltage AC Circuit Breakers
• GB/T 3804 3.6 kV–40.5 kV AC High-voltage Load Break Switches
• GB/T 3309 Mechanical Tests for High-voltage Switchgear at Normal Temperature
• GB/T 3906 3.6 kV–40.5 kV AC Metal-enclosed Switchgear and Controlgear
• GB/T 11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
• GB/T 13384 General Technical Conditions for Packaging of Mechanical and Electrical Products
• GB/T 16927.1 High-voltage Test Techniques
• DL/T 404 Ordering Technical Conditions for Indoor AC High-voltage Switchgear
• DL/T 593 Common Ordering Technical Guidelines for High-voltage Switchgear
Circuit Breaker Cabinet KEXGN-Z
Standard configuration and features:
• Vacuum circuit breaker
• Circuit breaker + isolating/earthing switch
• Isolating/earthing switch with manual or electric operating mechanism
• Complete five-prevention mechanical interlocking
• Live display with phase checking function
• Independent busbar room and cable room, each equipped with pressure relief flap
• Circuit breaker and three-position isolating/earthing switch have independent position indication
• Earthing busbar
Optional configuration and features:
• Reserved busbar extension
• Circuit breaker operating motor DC/AC220V
• Shunt trip coil: DC/AC 220 V
• Shunt closing coil DC/AC220V
• Bushing-type current transformer and ammeter, watt-hour meter
• Cable incoming double cables and surge arrester installation
• Auxiliary contacts: Circuit breaker position 4NO+4NC, maximum expandable to 8NO+8NC; Isolating switch position 2NO+2NC; Earthing switch position 2NO+2NC
• Secondary devices can be installed in the control box on top of the switchgear
Bus-tie / Riser Cabinet KEXGN-D
Standard configuration and features:
• Busbar
• Live display
Optional configuration and features:
• Interlocking device
• Current transformer
• Ammeter
• Heater
PT Cabinet
Standard configuration and features:
• Busbar
• Isolating/earthing switch with manual or electric operating mechanism
• Fully insulated, fully enclosed voltage transformer (PT)
• Live display with phase checking function
Optional configuration and features:
• Interlocking device
• Fuse
• Voltmeter
• Active power meter
• Reactive power meter
• Voltage changeover switch
• Primary harmonic elimination device
Certifications:
Product testing: KEXGN-40.5 gas insulated metal-enclosed switchgear has passed a full set of type tests at the Mechanical Industry High-voltage Apparatus Quality Testing Center and obtained a type test report.
RELATED PRODUCTS
Find Solutions, Not Just Suppliers
If you are interested in any of our products or would like to make your customized order, please feel free to contact us. We are looking forward to establish successful business relations with you.