XGN118-12 Environmental Gas Insulated Ring Main Unit
XGN118-12 environmental gas insulated ring main unit is the latest 10 kV distribution product independently developed by Shijiazhuang Kelin Electric Equipment Co., Ltd. The RMU houses the functional units and connecting busbars in a single gas tank filled with dry air, with no exposed live parts. It features a compact structure, fully insulated live parts, long service life, maintenance-free operation, a small footprint, high safety and immunity to environmental influences.
XGN118-12 Environmental Gas Insulated Ring Main Unit.pdf
Product Details
XGN118-12 environmental gas insulated ring main unit is the latest 10 kV distribution product independently developed by Shijiazhuang Kelin Electric Equipment Co., Ltd. The RMU houses the functional units and connecting busbars in a single gas tank filled with dry air, with no exposed live parts. It features a compact structure, fully insulated live parts, long service life, maintenance-free operation, a small footprint, high safety and immunity to environmental influences. Each unit of XGN118-12 environmental gas insulated ring main unit is divided into an instrument compartment, a mechanism compartment, a cable compartment and a gas compartment. The instrument compartment can house a microprocessor-based protection and control device (intelligent controller) and other instruments; the mechanism compartment houses a dedicated operating mechanism; the gas tank is made of 3.0 mm thick 304 stainless steel sheet, effectively resisting corrosion caused by moisture and salt spray. XGN118-12 environmental gas insulated ring main unit is widely used in industrial and residential ring-network and radial (terminal) supply applications. It is especially suitable for small secondary distribution stations, switching stations, industrial and mining enterprises, airports, railways, commercial areas, high-rise buildings, highways, subways, tunnels and other fields.
Key Features
Green and eco-friendly: dry air as the insulating medium — no SF6, no toxic or greenhouse gas emissions. Environmental protection during the entire production and operation process, high recyclability of materials at the end of life cycle.
Safe and reliable: The gas tank is filled with dry air at a slight positive pressure (relative pressure 0.02 MPa) and is hermetically sealed, minimising the risk of gas leakage. Insulation strength remains sufficient even at zero gauge pressure, without affecting normal operation. Strong environmental adaptability. All high-voltage components are sealed in a metal shell filled with dry air, and performance is not affected by external environmental factors. Especially suitable for harsh environments such as high altitude, severe cold, humidity, and pollution.
Low maintenance: High-voltage insulation is not affected by external environment and is not easy to age; vacuum switching technology makes and breaks short-circuit currents, eliminating the drawbacks of earthing switches, which cannot make earthing currents quickly and require maintenance after making short-circuits; the gas tank is made of 3.0 mm thick 304 stainless steel sheet, using fully automatic robotic welding; the most advanced helium mass-spectrometry leak detection method is used to detect gas leakage.
Technical Specifications
|
Model |
XGN118-12 |
Rated Voltage |
12kV |
|
Rated Current |
630A |
Rated Frequency |
50Hz |
|
Rated Short-circuit Breaking Current |
20 (25) kA |
Rated Short-time Withstand Current |
20 (25) kA for 4 s |
|
Rated Peak Withstand Current |
50(63)kA |
Rated Short-circuit Making Current (Peak) |
50(63)kA |
|
Resistance of the main circuit (per phase) |
≤ 140 μΩ |
Rated Operating Sequence |
O–0.3 s–CO–180 s–CO |
|
Mechanical Life |
Circuit Breaker/Load Switch: 10000 times; Isolating/Earthing Switch: 5000 times |
Electrical Life |
Circuit Breaker: 30 times; Earthing Switch Making: 5 times |
|
Auxiliary Circuit Rated Supply Voltage |
DC 24/48/110/220 V, AC 110/220 V |
Enclosure Protection Rating |
IP4X |
|
Gas Compartment Protection Rating |
IP67 |
Gas Rated Pressure (gauge, at 20 °C) |
0.02 MPa |
|
Annual Gas Leakage Rate |
≤ 0.01% per year |
Applications
Widely used in industrial and residential ring-network and radial (terminal) supply applications. Especially suitable for small secondary distribution stations, switching stations, industrial and mining enterprises, airports, railways, commercial areas, high-rise buildings, highways, subways, tunnels and other fields.
Scope of Use and Precautions
Applicable range:
Normal use conditions:
Ambient temperature: Maximum temperature: +40℃; Minimum temperature: -40℃
Ambient humidity: Daily average relative humidity: ≤95%; Monthly average relative humidity: ≤90%
Altitude: Not exceeding 3000m;
Seismic intensity: Not exceeding 8 degrees.
Typical Solution
Product Parameters
Design Features:
• Solidworks computer simulation solid modeling, virtual assembly;
• ANSYS electromagnetic field finite element analysis and optimization design;
• ADAMS 3D mechanism operation simulation, motion interference check;
• A visual observation window allows the visible isolating gap to be checked from the front of the unit.
• Standardized cable incoming/outgoing bushings and busbar connection bushings.
Specification Parameters:
Standards are cited without year designations; the latest editions apply.
• GB/T 311.1 Insulation Coordination for High-voltage Transmission and Transformation Equipment
• GB/T 1985 AC High-voltage Disconnectors and Earthing Switches
• GB/T 1984 High-voltage AC Circuit Breakers
• GB/T 3804 3.6 kV–40.5 kV AC high-voltage load break switches
• GB/T 3309 Mechanical Tests for High-voltage Switchgear at Normal Temperature
• GB/T 3906 3.6 kV–40.5 kV AC Metal-enclosed Switchgear and Controlgear
• GB/T 11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
• GB/T 13384 General Technical Conditions for Packaging of Mechanical and Electrical Products
• GB/T 16927.1 High-voltage Test Techniques
• DL/T 404 Ordering Technical Conditions for Indoor AC High-voltage Switchgear
• DL/T 593 Common Ordering Technical Guidelines for High-voltage Switchgear
• State Grid Standardized Design Customisation Scheme for 12 kV Ring Main Units (Boxes)
• China Southern Power Grid Bidding Technical Specifications.
• Auxiliary contacts: Auxiliary contacts can be equipped on all load switches and circuit breakers with 2NO+2NC indicating switch position. A shunt trip coil (AC or DC) can be installed on the transformer/circuit breaker. Low-voltage control components are located behind the front panel.
• Remote control and monitoring unit: Can be equipped with an integrated remote control and monitoring unit, adding a low-voltage box on top of the switchgear.
• Voltage indication: A capacitive voltage indicator shows whether the bushing is live; its socket can be used for phase checking.
• Short-circuit/earth fault indicator: To facilitate fault location, the cable switch module can be equipped with a short-circuit/earth fault indicator for simple fault detection.
• Electric operation: Manual operating mechanisms are standard for load switch and transformer units; electric operating mechanisms can be supplied as an option. Load switches, vacuum circuit breakers and earthing switches are all operated through mechanisms located behind the front panel. Both load switches and circuit breakers can be operated by operating handles (standard configuration), or can be equipped with motor operating mechanisms (accessories). However, the earthing switch can only be operated manually and is fitted with a mechanism capable of making fault currents.
• Cable connection: Cable connections use standard bushings at a uniform height above the floor, protected by a cable-compartment cover that can be interlocked with the earthing switch. For double cable incoming lines, a special double cable cover plate can also be used.
• Pressure indicator: Pressure indicators are usually equipped. The indicator is a pressure gauge; electrical contacts can be provided to set a low-pressure alarm threshold.
• External busbar: XGN118-12 can be equipped with extension busbars.
Certifications:
Product testing and technical appraisal: XGN118-12 environmental gas insulated ring main unit has passed a full set of type tests at the Mechanical Industry High-voltage Apparatus Quality Testing Center and obtained a type test report. XGN118-12 environmental gas insulated ring main unit passed the national-level technical appraisal meeting organized by the China Machinery Industry Federation in November 2016, reaching the international advanced level.